Published by on

General characteristics:
Proven simplicity of use
- 4 voltage input and 4 current input
- Inrush mode
- Unprecedented memory capacity
- Voltage and current ratios
Designed for inspection and maintenance teams in industrial or administrative buildings, this equipment can provide a snapshot of the main electrical network quality characteristics.
Capture and record all the parameters, transients, alarms and wave forms simultaneously.
Easy to handle and precise, these instruments also offer a large number of calculated values and several processing functions.
Specifications:
Measurements |
|
Number of channels |
4U / 4I |
Voltage (TRMS AC+DC) |
|
Phase-Phase |
6 V to 960 V 10 V to 1,000 V |
Phase-Neutral |
6 V to 480 V 10 V to 1,000 V |
Voltage ratio |
Up to 500 kV |
Current (TRMS AC+DC) |
100 mA to 6,500 A |
MN clamps |
MN93: 2 to 240 Aac ; MN93A: 0. 005 Aac to 5 Aac / 0.1 Aac to 120 Aac |
C193 clamp |
3A to 1,200 Aac |
AmpFLEX or MA clamps |
30 A to 6,500 Aac |
PAC93 clamp |
10 A to 1,000 Aac / 10 A to 1,400 Adc |
E3N clamp |
50 mA to 10 Aac/dc 100 mA to 100 Aac/dc |
Current ratio |
10 mA to 50 kA |
Frequency 40 Hz to 69 Hz |
40 Hz to 69 Hz |
Power values |
W, VA, var, PF, DPF, |
Energy values |
Wh, varh, VAh |
Harmonics |
Yes |
THD |
yes, orders 0 to 50, phase |
Expert mode |
Yes |
Transients |
210 |
Flicker |
Yes |
Inrush mode |
Yes, > 1 minute |
Unbalance |
Yes |
Recording Min/Max recording |
Yes |
of all parameters at max .sampling rate of a selection of parameters with acquisition every 10 min |
1 month Several years |
Alarms |
10,000 of 40 different types |
Recognition of current sensors |
9 |
Peak |
Yes |
Vectorial representation |
Automatic |
Display |
Colour ¼ VGA LCD screen, 320 x 240, diagonal 148 mm |
Capture of screens and curves |
50 |
Electrical safety |
IEC 61010 1,000 V CAT III / 600 V CAT IV |
Languages |
25+ |
Communication interface |
USB type B |
Power supply |
9.6 V NiMH rechargeable battery or external mains |
Dimensions |
240 x 180 x 55 mm |
Weight |
1.9 kg |