General characteristics
Measurement of all powers
Electric engine maintenance
Measurement of very weak and very strong currents
Phase shift analysis
Measurement of engine start-up current
Simultaneous access to all measurement modes
The equipment is designed for tradesmen and installers working in the construction industry and maintenance departments. The broad range of measurements it provides also makes it ideal for technical and technological teaching.
Extremely easy to use, it is suitable for testing electrical installations, especially if they are equipped with systems based on power electronics.
Suitable for use on the ground, it can also be used on a tabletop, thanks to its retractable support.
User-friendly, it has a large graphic screen and automatically recognises the type of sensor connected
MAIN MEASUREMENTS
■ Voltage & current:
■ Complete analysis of power and energy:
■ Recording period up to several days:
■ Personalised setting of alarms:
TECHNICAL FEATURES
Voltage range
|
from 6 VRMS to 600 VRMS AC+DC ±(0.5%+2pts)
|
AC current range |
from 5mA to 6500 A ±(0.5%+1pts) |
DC current range |
from 1 A to 1700 A ±(1%+1pts) |
Mini, Maxi, Avge., Peak values (+ and -), CF |
Yes
|
Fundamental frequency |
from 40 Hz to 70 Hz |
Screen |
Backlit 173-segment LCD |
Single-phase and three-phase balanced |
Yes
|
W, VA, var powers, DF, THD, Cosφ |
Yes |
varh and VAh energy |
— |
Harmonics (IEC 1000-4-7) |
Up to 50th order |
Recordings |
— |
Alarms |
— |
Flicker PST (IEC 1000-4-15) |
— |
Engine rotation speed |
from 6 RPM to 120 kRPM ±(0.5%) |
Temperature (Pt100) |
from – 200°C to 850°C ±(1%+10pts) |
Resistance (coiling) |
from 0.0 Ω to 2000 Ω ±(0.5%+1Ω) |
Phase rotation
|
Yes, with display of phase order in three-phase |
Measurement storage |
Yes |
Use • Ambient temperature • Moisture content (relative) |
23°C ±3K (45% ; 75%) |
Protection factor |
IP54 |
RS232 Port |
Yes Có |
IEC 61010-1 |
600 V, Cat. III |
Weight |
840 g (with batteries) |
Dimensions |
211 x 108 x 60 mm |